Schematics
AutoCAD, AutoCAD Electrical, or EPLAN native files, or PDFs. Native files let us return redlines in your format.
Build to print
Send us your schematics, layout, and BOM. We review them, raise questions in writing, build to UL 508A, test, and ship with your redlines. Nothing changes without your approval.

Your package
The more complete the package, the tighter the quote. Partial packages are fine; we’ll list what we assumed.
AutoCAD, AutoCAD Electrical, or EPLAN native files, or PDFs. Native files let us return redlines in your format.
Backplate and door layouts with dimensions. If there is no layout, we can produce one from the schematics.
Manufacturer and part number for each line, with quantities. Tell us which items you will furnish.
Supply voltage, available fault current or required SCCR, and enclosure type rating.
Wire numbering, device tags, nameplate content, and label material if your project specifies them.
Whether we write the PLC program or you supply one for I/O checkout, and who will witness FAT.
Drawing review
A review costs a few hours. Finding the same problem on the backplate costs days.
Every device on the drawings is on the BOM with the right rating, and every BOM line appears on the drawings.
Component dimensions, wire duct fill, heat sources, and manufacturer clearances for drives and power supplies.
The lowest-rated component in each power circuit identified, and the resulting panel SCCR checked against the stated fault current.
Conductor sizing and protection, disconnect requirements, spacing, and grounding checked against UL 508A and NFPA 79 where it applies.
Material
If a part is unavailable or on long lead, we propose an alternate in writing with the impact on SCCR, footprint, and wiring. You approve or reject it.
PLCs, drives, or HMIs you supply are received, inspected, and logged against your BOM, with photos of anything damaged in transit.
Allen-Bradley and alternates such as Siemens, Schneider, Eaton, or Phoenix Contact, whatever your BOM or site standard calls for.
Redlines
Any change agreed through an RFI is marked on the drawings during the build, not reconstructed afterwards.
Redlines come back in PDF, or in your native format if you sent native files, so your as-builts stay in your system.
We don’t replace your title block or add our name to your drawings.
Next step
Send the package, the quantity, and the date you need panels. We’ll reply with questions or a quote timeline.